I'm designing my first RV Park. The pedestals my customer wants are offered by more than one manufacturer and are very similar. They have a 2P50A, a 1P30A, and a 1P20A breaker with one receptacle each. Very common set-up. The breakers inside the pedestal are fed from a single phase 240V...

Now we have an earth pedestal combo with a meter (20A, 30A, 50A built in) we want to put in with a direct bored conduit from a transformer or H.H. The inspector is saying we need to swap out the standard 30sp and 50dp breakers with GFCI equivalent. Inspectors are quoting 210.8 specifies 150V to ground or less need GFCI but here is my problem.

pedestal for washing machine and dryer 2

2020 NEC 551.71(F) : GFCI at new RV Pedestal, inspectors want 50A and ...

pedestal for washing machine and dryer 3

The service pedestal qualifies as a structure and any wiring from that point of main disocnnect becomes a feeder. To be real concise, we dont know that the disconnecting means for the house is located remotely - If it were located nearest the point of entry then 250.32 (D) wouldnt come into play.

pedestal for washing machine and dryer 4

From service pedestal to house...3 or 4 wire? | Information by ...

1st ISSUE Is a grounding electrode required for an RV pedestal that has a 50 amp breaker and receptacle with a 20 amp receptacle and breaker? If my understanding is correct it is not required based on 2020 250.50 as the GE is required for each building or structure and in definitions the...

Looking for a quality 120-volt outdoor power post/pedestal. I want something better than the old school 4x4 wood post with bell box and heavy duty cover...